Customized Products
Fire Resistant & Armoured Fieldbus Cable
Construction:
Pair No. X Conductor Size | 1PX18AWG |
---|---|
Conductor | 7 Strands tinned copper |
Fire Barrier | MICA Tape |
Insulation | XLPE |
Shielding | Aluminium foil |
Drain Wire | Tinned copper wire |
Inner Sheath | LSZH |
Amour | Galvanised steel wire |
Outer Sheath | LSZH |
Nominal Overall Diameter | 17.5+/-2.0mm |
Approx. Weight | 385 KG/KM |
Core Color | Blue&Orange, other color is available upon request. |
Sheath Color | Orange,other color is available upon request. |
Electrical Data:
Characteristic Impedance @ 31.25KHz | 100 Ω ± 20Ω |
|
---|---|---|
Conductor Resistance | 23.5 Ohm/km max. |
|
Test Voltage | 1.0KV |
|
Operate Voltage | 300V |
|
Mutual capacitance | 80 pF/m |
|
Max. Attenuation | 39KHz |
3.0dB/km |
Technical Data:
Min. Bending Radius | 10 x OD mm |
---|---|
Operating Temp.Range, min. | -40 °C |
Operating Temp.Range, max. | +90 °C |
Fire Performance:
Circuit Integrity | IEC 60331 |
---|---|
flame Retardance (single vertical wire or cable test) | Iec 60332-1-2; en 60332-1-2 |
Reduced fire Propagation (Vertically-mounted bundled wires & cable test) |
Iec 60332-3-24; en 60332-3-24 |
Halogen free | Iec 60754-1; en 50267-2-1 |
no corrosive Gas emission | Iec 60754-2; en 50267-2-2 |
Minimum smoke emission | Iec 61034-2; en 61034-2 |